1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Delta Electronics
- Equipment: InfraSuite Device Master
- Vulnerability: Deserialization of Untrusted Data
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow remote code execution.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Delta Electronics products are affected:
- InfraSuite Device Master: Versions 1.0.10 and prior
3.2 Vulnerability Overview
3.2.1 Deserialization of Untrusted Data CWE-502
Delta Electronics InfraSuite Device Master contains a deserialization of untrusted data vulnerability because it runs a version of Apache ActiveMQ (5.15.2) which is vulnerable to CVE-2023-46604.
CVE-2023-46604 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2023-46604. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Taiwan
3.4 RESEARCHER
An anonymous researcher wor
[…]