1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Rockwell Automation
- Equipment: FactoryTalk ThinManager
- Vulnerabilities: Missing Authentication For Critical Function, Out-of-Bounds Read
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to send crafted messages to the device resulting in database manipulation or a denial-of-service condition.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Rockwell Automation FactoryTalk product versions are affected:
- ThinManager: Versions 11.2.0 to 11.2.9
- ThinManager: Versions 12.0.0 to 12.0.7
- ThinManager: Versions 12.1.0 to 12.1.8
- ThinManager: Versions 13.0.0 to 13.0.5
- ThinManager: Versions 13.1.0 to 13.1.3
- ThinManager: Versions 13.2.0 to 13.2.2
- ThinManager: Version 14.0.0
3.2 Vulnerability Overview
3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306
An authentication vulnerability exists in the affected product. The vulnerability could allow a threat actor with network access to send crafted messages to the device, potentially resulting in database manipulation.
CVE-2024-10386 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-10386. A base score of 9.3 has been calculated; the CVSS vector string is (This article has been indexed from All CISA Advisories