Rockwell Automation FactoryTalk View Site Edition

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk View Site Edition
  • Vulnerability: Incorrect Permission Assignment for Critical Resource

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow any user to edit or replace files, which are executed by account with elevated permissions.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports that the following versions of FactoryTalk, an HMI application, are affected:

  • FactoryTalk View SE: version 13.0

3.2 Vulnerability Overview

3.2.1 Incorrect Permission Assignment for Critical Resource CWE-732

A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions.

CVE-2024-7513 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-7513. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Chemical, Commercial Facilities, Critical Manufacturin

    […]
    Content was cut in order to protect the source.Please visit the source for the rest of the article.