Rockwell Automation Pavilion8

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 8.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: Pavilion8
  • Vulnerability: Improper Authentication

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to retrieve other user’s sessions data.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Rockwell Automation Pavilion8, a model predictive control software, are affected:

  • Pavilion8: versions v5.17.00 and v5.17.01

3.2 Vulnerability Overview

3.2.1 IMPROPER AUTHENTICATION CWE-287

The JMX Console within the Pavilion is exposed to application users and does not require authentication. If exploited, a malicious user could retrieve other application users’ session data and or log users out of their sessions.

CVE-2023-29463 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported these vulnerabilities to CISA.

4. MITIGATIONS

Rockwell Automation recommends customers apply the following mitigations:

Rockwell Automation encourages customers using the affected software are encouraged to app

[…]
Content was cut in order to protect the source.Please visit the source for the rest of the article.

This article has been indexed from All CISA Advisories

Read the original article: