Schneider Electric Modicon

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Modicon M241 / M251 / M258 / LMC058
  • Vulnerability: Improper Input Validation

2. RISK EVALUATION

Successful exploitation of this vulnerability could lead to a denial-of-service and a loss of confidentiality and integrity in the controller.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports that following Modicon PLCs are affected:

  • Modicon Controllers M241: All versions
  • Modicon Controllers M251: All versions
  • Modicon Controllers M258: All versions
  • Modicon Controllers LMC058: All versions

3.2 Vulnerability Overview

3.2.1 IMPROPER INPUT VALIDATION CWE-20

An improper input validation vulnerability exists that could lead to a denial-of-service and a loss of confidentiality and integrity in the controller when an unauthenticated crafted Modbus packet is sent to the device.

CVE-2024-11737 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-11737. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).